Two steel warehouse buildings with the same eave height can have different usable storage heights. The haunch deepens the rafter near the column. Farther into a bay, lighting, ducts or sprinkler pipework may set the lowest obstruction. A rack layout that fits in plan can fail in section.
Is there a standard warehouse clear height?
Start with the finished floor and the highest operating position of the load, including its pallet. Mark the lift path and the clearance required by the equipment manufacturer. Check the outer rack aisle and the approach to the loading door separately.
Measure at the working position
Suppose the underside of steel is 7.2 m above the finished floor at one rack position. A duct below the rafter is 6.8 m above the floor. The initial geometric limit at that point is 6.8 m. Allowable operating height still depends on equipment clearance, structural deflection and the fire protection design. Moving the rack one bay can change which obstruction controls.
What to put on the drawing
Label the floor datum, grid reference, minimum clearance and operating condition. Ask the structural designer to check relevant deflections and the services coordinator to overlay installed levels. Before commissioning the racks, measure the clearance at the same grid reference and record it on the as-built section.